Description
Features and benefits
- Explosion protection to
-CENELEC
-IEC - GRP enclosure (glass fibre-reinforced polyester resin).
- Seven types of enclosure.
Technical data
Exposion-proof Distribution Boxes HLDP03-Q
Explosion protection | |
Gas explosion protection | ![]() |
Dust explosion protection | ![]() |
Conformity to standards | EN 60079-0:2012,EN60079-1:2007,EN60079-31:2009 |
IEC 60079-0:2011,IEC60079-1:2007,IEC60079-31:2008 | |
Enclosure material | Aluminium alloy; powder coated surface |
Enclosure colour | gray-white with mental lines |
Exposed fastener | Stainless steel |
Components | MCB (mini circuit breaker) |
AC contactor | |
Thermal overload relay | |
Indicator, pushbutton | |
Rated voltage | Max.415V AC 50/60Hz |
Degree of protection | IP66 |
Ambient temperature | -60℃~+55℃ |
Cable entries | Standard M□×1.5 pluy;See selection table as below |
Entry direction | Bottom |
Selection table
Type | Control motor power(kw) | Rated current of circuit breaker(A) | Adjustable range of setting current of thermal relay (A) | Rated current of contactor (A) | Setting value of delay time | Cable entry size |
HLDP03-Q4/16/7~10/(N) | 4 | 16 | 7~10, le=8.5 | 9 | — | 2×M25×1.5 |
HLDP03-Q5.5/20/9~13/(N) | 5.5 | 20 | 9~13, le=11 | 12 | 2×M25×1.5 | |
HLDP03-Q7.5/25/12~18/(N) | 7.5 | 25 | 12~18, le=16 | 18 | 2×M32×1.5 | |
HLDP03-Q11/32/16~24/(N) | 11 | 32 | 16~24, le=23 | 25 | 2×M32×1.5 | |
HLDP03-Q15/40/23~32/(N) | 15 | 40 | 23~32, le=30 | 32 | 2×M32×1.5 | |
HLDP03-Q18.5/50/30~38/(N) | 18.5 | 50 | 30~38, le=36 | 40 | 2×M40×1.5 | |
HLDP03-Q22/63/37~50/(N) | 22 | 63 | 37~50, le=46 | 50 | 2×M40×1.5 | |
HLDP03-Q18.5/50/30~40/(Y) | 18.5 | 50 | 30~40, le=36 | — | 13s | 2×M40×1.5 |
HLDP03-Q22/63/37~50/(Y) | 22 | 63 | 37~50, le=46 | 15s | 2×M40×1.5 | |
HLDP03-Q30/80/48~65/(Y) | 30 | 80 | 48~65, le=60 | 17s | 3×M50×1.5 | |
HLDP03-Q37/100/63~80/(Y) | 37 | 100 | 63~80, le=75 | 18s | 3×M50×1.5 | |
HLDP03-Q45/125/80~104/(Y) | 45 | 125 | 80~104, le=90 | 20s | 3×M63×1.5 |